Modbus TCP

A driver: {type: modbus} section puts a manifest project on the oldest field bus that is still everywhere: PID loops behind a gateway, VFDs, gas analysers, power meters, IO-Link masters. Everything the driver polls comes from one hand-written device map — register maps off the datasheet once per device type, hosts and unit-ids once per instance — which nautilus modbus import turns into a committed manifest and a committed tag file. Shape: a manifest-tier io.Driver, mirroring nautilus eip import end to end.

driver:
type: modbus
manifest: modbus_manifest.yaml # from `nautilus modbus import`
scan-rate: 1s # the default scan class
scan-classes: { fast: 500ms, slow: 2.5s }
tag-classes:
fast: ["FAN_*"]
slow: ["*_Totals"]
tag-files: [tags/modbus.yaml]

manifest: is the only required key — a project missing it fails nautilus check, not nautilus run, so a bad config never reaches the field. New never dials: it decodes the manifest, validates every cross-reference and format, and computes the block-read plan offline, so nautilus check and nautilus build pass in CI with no device in sight. The connection is Start’s job.

Generating the manifest: nautilus modbus import

Section titled “Generating the manifest: nautilus modbus import”

The one file you write by hand is the device map. It describes device types once — the register map, formats, scaling, word order, straight off the datasheet — and instances per physical device or gateway drop — host, unit-id, overrides:

devices.yaml
devices:
temp-controller:
description: PID temperature controller behind a Modbus TCP gateway
scan-class: slow
registers:
- {tag: Tpv, address: 0, format: int32, scale: 0.1, unit: degC, desc: process temperature}
- {tag: Tsp, address: 262, format: int32, scale: 0.1, writable: true, rewrite: 2.5s, init: 0.0, unit: degC, desc: temperature setpoint}
- {tag: AlmH, address: 12, table: discrete, desc: high temperature alarm}
analyser:
word-order: little
timeout: 2s
max-block: 64
registers:
- {tag: CH1, address: 0, format: float32, unit: ppm, desc: channel 1}
- {tag: CH2, address: 2, format: float32, unit: ppm, desc: channel 2}
instances:
- {id: TC_A, type: temp-controller, host: 192.168.10.10, unit-id: 1, enable-tag: CFG_HeatersOn, desc: zone A loop}
- {id: TC_B, type: temp-controller, host: 192.168.10.10, unit-id: 2, enable-tag: CFG_HeatersOn, desc: zone B loop}
- {id: GAS, type: analyser, host: 192.168.10.51, unit-id: 4, desc: stack analyser}

Two loops on one host with different unit-ids is the gateway shape — an Anybus or a Moxa fronting several serial devices is one source per drop, same host. A plain TCP device is just an instance whose unit-id nobody cares about.

Terminal window
nautilus modbus import --map devices.yaml

That emits two committed, never-hand-edited files, byte-identical on every re-run so a regeneration diffs cleanly:

  • modbus_manifest.yamlsources: (host, unitid, wordorder, timeout, enable, maxblock) and tags: (source, table, address, format, scale, writable/rewrite/writeonly, scanclass). Decoded strictly — a misspelled key is an error with a did-you-mean, not a silently dropped binding.
  • tags/modbus.yaml — an ordinary tag file (role: input|output, unit, desc, init), composed with tag-files: [tags/modbus.yaml].

The regeneration command lives in each generated file’s header, so nobody has to remember it. Useful flags: --instance for one instance id, --tags / --writable globs to select and mark, --tags-skip to leave tags the project declares by hand out of the tag file, --out and --tags-out for paths, --plan to print the block plan.

nautilus modbus tags modbus_manifest.yaml --map devices.yaml re-derives just the tag file from an already-committed manifest. Without --map it still works; the unit/desc/init columns, which only the map knows, are dropped.

tentacle-era drivers issued one Modbus request per variable per interval. A sixteen-register analyser then costs sixteen round trips a second. The planner coalesces every binding on the same (source, table, scan class) into as few block reads as the protocol allows:

Terminal window
nautilus modbus import --map devices.yaml --plan
source GAS: 2 blocks
FC3 holding 0..7 (8 registers, class default): GAS_CH1@0, GAS_CH2@2, GAS_CH3@4, GAS_CH4@6
FC4 input 0..1 (2 registers, class default): GAS_Flow@0
source TC_A: 3 blocks
FC3 holding 0..9 (10 registers, class slow): TC_A_Tpv@0, TC_A_MV@8
FC3 holding 262..263 (2 registers, class slow): TC_A_Tsp@262
FC2 discrete 12..12 (1 coils, class slow): TC_A_AlmH@12

Four float32 channels become one FC3 request. Every tag prints with its address so a commissioning tech can check it against the datasheet.

Three knobs shape the plan:

  • Gap. A block may span up to 8 unaddressed registers rather than pay for a second round trip — reading eight unused words is cheaper than another request. WithBlockGap(0) never bridges a hole, the escape hatch for devices that fault a read touching an unimplemented register.
  • max-block. Caps one read for devices that reject long ones (some ADAM firmware stops at 64). Absent, the protocol maxima apply: 125 registers per FC3/FC4, 2000 coils per FC1/FC2.
  • Scan classes. A binding’s scan-class names its poll group; unassigned bindings are the default class, whose rate is scan-rate. The reserved class none catalogs a tag without ever polling it — a command register the program only writes belongs there. tag-classes: globs override the generated class from nautilus.yaml, so re-running the import never erases polling policy.

Addresses are 0-based PDU addresses. What a datasheet calls 40001 is holding address 0; 30001 is input address 0. No option flips this — see Not supported. nautilus modbus browse --from takes the same 0-based address, so the number you type there is the number you put in the map.

Tables are holding, input, coil, discrete. Holding and coil are writable; input and discrete are read-only in the protocol itself, and marking one writable is a validation error.

Formats: int16, uint16, int32, uint32, float32, float64, bool, and bit:N for one bit (0..15) of a register. Bit tables take only bool. Scaling is engineering = raw * scale + offset, applied on read and inverted on write; scale: 0 means 1, so an unset field is the identity rather than a zeroed tag.

Word and byte order are per source, not global, because the same hardware ships both ways:

sources:
- id: GAS
host: 192.168.10.51
unitid: 4
wordorder: little # big (default) | little — register order of a multi-register value
byteorder: big # big (default) | little — byte order inside each register

wordorder reverses the register sequence of a 32- or 64-bit value; byteorder swaps the two bytes inside each register. If a float32 reads as garbage whose magnitude still looks plausible, flip wordorder first — nautilus modbus browse settles it in seconds by printing every candidate format side by side.

Each source gets a driver-synthesized <source>__Online BOOL input, true while its connection is up. It is present from Start — before any poll has landed — so interlock logic can gate on it safely:

GasAlarm := GAS__Online AND GAS_CH1 > 250.0;

not GasAlarm := GAS_CH1 > 250.0 alone. Data tags stay absent from the snapshot until their block has been read at least once.

A source may also name an enable: tag — any BOOL the project already declares. While it is false the source is parked: no connection is attempted, its tags hold their last values and report Stale (NotConnected if they were never delivered). Setting it true wakes the source immediately. The enable tag is a command to the driver, not a register write: it acts even while the write gate is closed, and it appears in OutputNames() alongside the writable bindings.

Modbus has two entirely different kinds of failure, and the driver treats them differently on purpose.

An exception response — the device answered and refused: illegal data address, illegal function, gateway target failed to respond. The connection is fine and this span of addresses is wrong. That block’s tags go Bad, its siblings on the same device stay Good, and the driver keeps polling — it does not reconnect over a bad register map. Three consecutive exceptions park just that block for one retrymin period so a permanently illegal address stops burning a request slot every cycle; it retries after that. The refusal surfaces as badBlocks on the device row.

A transport failure — dial refused, timeout, a short read, a response carrying the wrong unit id. The whole source is down: the driver drops the connection and reconnects with exponential backoff from retrymin (1s) to retrymax (60s), resetting on success. Values hold. Nothing is zeroed and nothing is invented; a tag delivered at least once reports Stale with its age, a tag never delivered reports NotConnected, and <source>__Online goes false.

Quality is reported through io.QualityReporter, non-Good entries only — a healthy plant reports an empty map. Quality is source-scoped: one dead device takes exactly its own tags stale, never the plant’s. The __Online companions are the driver’s own truth and are always Good.

A writable: true binding on a holding or coil table becomes a role: output tag whose writes reach the device as FC 5/6/15/16.

Outputs are commands; an unchanged output since start is not a command. An output’s value before anyone writes it is its init: — usually zero — and taken at face value, a controller restarting against a running plant would command every setpoint to zero. So the first snapshot after Start is the baseline: recorded, sent to nobody. Thereafter only a value that actually moved goes on the wire, once. A command raised while the source is down is queued per source (latest value per tag) and flushed on reconnect, counted as queuedWrites on the device row.

rewrite: is the exception, and it is a keep-alive. Some devices watch a command register and fail safe if it stops moving — a safety controller’s enable word, a VFD control word, an IO-Link master’s Modbus watchdog. A binding with rewrite: 2.5s re-asserts its last commanded value on that period even when nothing changed, and its baseline value is written on connect, because a watchdog that never sees a first write drops out immediately.

- {tag: Tsp, address: 262, format: int32, scale: 0.1, writable: true, rewrite: 2.5s, init: 0.0}
- {tag: Control, address: 2100, writable: true, write-only: true, init: 0.0}

write-only takes a writable binding out of the read plan, for the rare register that cannot be read back (some drive control words). Without it a writable binding is also polled, and the read-back is the source of truth after a restart — which is what you want almost always.

Writes are coalesced: exactly adjacent register writes staged in one flush merge into a single FC16 run, adjacent coils into one FC15, and a lone register or coil goes as FC6 or FC5. Requests on a source are strictly sequential — Modbus TCP permits pipelining by transaction id, but the gateways in the field do not, so one outstanding request is the default.

Kind: "modbus", with one device row per source{ID: "TC_A", Online: true, Detail: "3 blocks"}, or "3 blocks · 1 refused" when a block is exception-marked. The driver state climbs connectingerror (nothing answers) → degraded (a source dark, or any block refused) → connected, plus waiting when every source is parked by its enable tag. Metrics: sources (connected / total), blocks, reads, writes, errors, and queued writes when any command is parked.

Extra["sources"] carries the structured twin of the rows — id, addr, state (connected | connecting | error | parked), sinceMs, blocks, badBlocks, queuedWrites, rttMs (an EWMA of request round-trip), retries, exceptions. That is the shape DriverStatusPanel and DriverStatusCard already render for an eip driver, so a Modbus project’s comms status needs zero HMI changes.

The in-repo slave stands in for a whole plant on one listener, multi-unit like a real gateway, built from the manifest alone:

Terminal window
nautilus modbus serve --manifest modbus_manifest.yaml --values seed.json --ramp

--values is a JSON {tag: value} file in engineering units — serve inverts each binding’s scaling and word order on the way into the registers, so you write "GAS_CH1": 120.0, not a pair of raw words. --ramp drifts the numeric inputs so trends look alive. --listen defaults to 127.0.0.1:5020. Point the manifest’s hosts at it and nautilus run . polls the same plan --plan printed.

browse is the commissioning poke — read a range from a live device (or the bench) and see every address raw and decoded:

Terminal window
nautilus modbus browse --host 127.0.0.1 --port 5020 --unit 4 --from 0 --count 8
nautilus modbus browse --host 192.168.10.51 --unit 4 --word-order little --format float32 --count 8

Without --format it prints every format side by side, which is how you find a device’s real word order in one shot. Other flags: --table (holding | input | coil | discrete), --timeout.

A skid is rarely the whole plant. When the same controller also consumes a Sparkplug fleet, or polls a Logix PLC over EtherNet/IP, list the drivers instead of picking one — drivers: is the plural of driver:, each entry the same shape:

drivers:
- type: modbus
manifest: modbus_manifest.yaml
scan-classes: { fast: 500ms }
- type: sparkplug-host
name: fleet # optional; default is the type, deduped as "eip-2"
broker: "tcp://mqtt.plant:1883"
group-id: Plant
host-id: plant-scada
manifest: sparkplug_manifest.yaml
tag-files: [tags/modbus.yaml, tags/sparkplug.yaml]

Reads fan out to every driver and merge; a write goes to the one driver whose bindings claim the tag. Ownership is disjoint by construction: a tag delivered by two drivers, or writable through two, is a load error naming bothnautilus check reports it offline, the same no-last-wins rule tag files keep. Setting driver: and drivers: together is an error too; move the single driver into the list. On /api/drivers each driver keeps its own row (the Modbus one still has a device row per source), quality merges per tag, and a Sparkplug device: on the same controller is healthy only when every child bus is — an operator reading the device online should be able to trust all of its tags, not the subset whose bus is up. The memory loopback cannot join a list: it owns whatever is written to it, which is exactly what makes it unroutable next to another driver.

With a redundancy: section, the driver’s write gate is wired to leadership — commands leave the driver only on the leader, and a SetWriteGate func can compose a “logic healthy” signal into the same condition.

A closed gate stops the rewrite: re-asserts too, by design. A device whose keep-alive word goes quiet trips its own fail-safe, which is exactly what must happen when this replica is not the leader or its logic is faulted. A hung controller that kept refreshing a stale command would mask the fault instead, leaving the device happily executing a setpoint nobody computes any more. Reads are unaffected on both replicas.

nautilus test never opens a socket. Keep a memory.yaml beside nautilus.yaml with the same tags and driver: {type: memory}, and the acceptance suites run in virtual time against the loopback driver:

Terminal window
nautilus check -m memory.yaml .
nautilus test -m memory.yaml .

given: writes the driver’s input image exactly the way a block read would, so the same *_test.yaml files pass unchanged once the real driver is polling — a ten-second interlock or a PI loop’s settling time asserted deterministically, in milliseconds, on a laptop with nothing on the network.

The wire layer gets a second opinion: CI runs the driver against a pymodbus server — a foreign implementation, not our own slave — seeded with known raw words for every format in both word orders across all four tables, plus an unimplemented range that answers exception 0x02. It asserts that a foreign encoder agrees with ours, that each writable format round trips, that the refused range marks its block bad while siblings stay Good, and that a slow response drives the reconnect path with values held.

  • Modbus RTU and ASCII over serial. TCP only. A serial device reaches nautilus through a TCP gateway, which is the deployed shape anyway — and the gateway’s drops are one source each.
  • BCD, int64, and string formats. The set is int16, uint16, int32, uint32, float32, float64, bool, bit:N.
  • One-based addressing. There is no --one-based or base: 40001 option, and there will not be: addresses are 0-based PDU addresses everywhere — map, manifest, browse, and the plan output — so there is exactly one convention to hold in your head. Subtract once, in the map.
  • Pipelined requests. One outstanding request per source, because the gateways in the field do not pipeline reliably.

The manifest section is the manifest form of the modbus package — a custom topology, or polling policy computed rather than configured, uses it directly as an io.Driver:

import "github.com/joyautomation/nautilus/modbus"
m, err := modbus.ParseManifest(manifestYAML)
driver, err := modbus.New(m,
modbus.WithScanRate(time.Second), // the default class
modbus.WithScanClass("fast", 500*time.Millisecond),
modbus.WithScanClass("slow", 10*time.Second),
modbus.WithTagClass("fast", "FAN_*"), // globs on tag names
modbus.WithTagClass(modbus.NoPoll, "*_Control"), // cataloged, never polled
modbus.WithBlockGap(0), // never bridge a hole
modbus.WithLogger(slog.Default().With("driver", "modbus")),
)
driver.Start(ctx)
rt, err := runtime.New(runtime.Options{
Program: program,
Driver: driver,
Inputs: driver.InputNames(),
Outputs: driver.OutputNames(),
})

WithDialer substitutes the TCP dial, which is how the tests hand the driver an in-process slave or a recording wrapper that asserts what hits the wire. driver.Plan() returns the computed block plan, Health() the per-source rows behind /api/drivers, and SetWriteGate the redundancy hook described above. Stop closes every source’s connection; New never opened one.