Streaming and data quality

Two things separate a demo HMI from one a plant runs on: how much of the tag store it has to pull to draw a screen, and whether it can tell a live number from an old one. This guide covers both, because they are the same conversation — what the controller says on every tick, and what it means.

The numbers this page is built on come from a real 10,000-tag controller: GET /api/state was 571 KB, and a single SSE client pulled about 2 MB every ten seconds — four complete renderings of the plant per second, whether or not anything moved. That is fine for the one wall screen it was built for. It does not survive a shift’s worth of tablets, and there is no version of “add more clients” that gets better.

Ask for them with ?delta=1:

GET /api/stream?delta=1

The first frame is a complete snapshot. Every frame after it carries only the tags whose value changed since the previous frame sent to that client:

// first frame
{"ts":1770000000000,"seq":1,"full":true,"tags":{ /* all 10,000 */ },"scan":{}}
// every frame after
{"ts":1770000000250,"seq":2,"tags":{"RTU9_WEL15_LIT_001":4.31},"scan":{}}

Two fields make it a protocol rather than a trick:

  • seq — this client’s frame counter, from 1, reset on every new connection.
  • fullreplace your state, don’t merge into it. True on the first frame, on each periodic resync (30 s by default), and whenever the controller’s set of tag names changed, which is the one difference a delta cannot express: there is no way to say “this tag is gone”.

Everything else on the frame — the scan diagnostics, driver status, alarm counts — is gated the same way, once the client says it can merge them. That is the frame floor, below.

Measured on 10,000 plant-shaped tag names, with the scan diagnostics included in both (go test ./server/ -run XXX -bench FrameBytes):

Churn per tickFull frameDelta frameRatio
1 %284 KB5.5 KB51× smaller
5 %284 KB16.8 KB17× smaller
20 %284 KB59 KB4.8× smaller

Five percent is a realistic steady state for a plant that is running rather than starting up. The floor those numbers cannot go below is the diagnostics block (~3 KB here), which is why the 1 % row is 51× and not 280× — and which is what the frame floor removes.

The server side gets cheaper, not more expensive, because the per-tick work is shared: one sweep of the store for all delta clients, one rendering of each changed value, and one JSON encoding per distinct (generation, filter) pair — and clients tick together, so that is usually one encoding for the whole fleet. At fifty connected clients a delta broadcast costs about a tenth of what a full broadcast does.

This is the part worth trusting, because a merge that quietly goes wrong does not throw or blank a screen — it leaves one number frozen at whatever it last was, on a page that otherwise looks alive.

The server tracks, per client, the store generation that client has been brought up to date at (see write generations — the whole delta mechanism is one uint64 per client, and “what changed since” is one integer comparison per tag with no value comparison anywhere). That generation advances only when a frame is actually enqueued. The broadcast loop drops frames for a client too slow to keep up — it must, or one tablet on bad wifi stalls the loop — and a dropped frame simply leaves the generation where it was, so the next frame carries what the dropped one would have.

A dropped frame therefore costs latency, never content. Which means a skipped seq cannot mean “a frame went missing” — it can only mean the transport mangled the stream. The client’s response is to reconnect, which yields a fresh full frame by construction. It never negotiates a repair with a transport that has already proved unreliable.

The periodic resync is not a crutch for that argument; it is the bound on how long a client can stay wrong if something outside the argument ever does go wrong. Tune or disable it with server.Options{ResyncInterval: …} (negative disables).

A client that asks for nothing gets exactly the stream this endpoint has always served: whole frames, no seq, no full. The frame shape is a public API with clients this repo does not own, and switching them to partial frames would corrupt every one of them in a way that looks like the plant went quiet rather than like a protocol change.

?full=1 forces whole frames even alongside ?delta=1 — the escape hatch for a client with reason to distrust its own merge.

Tag filters and tag deltas both shrink the same part of the frame, and on the WRD host they eventually ran into what was left. Every frame carried ~17.9 kB that had nothing to do with tags:

BlockSizeWhy it moves
drivers~12.8 kB55 Sparkplug device rows plus the host’s own per-node roster in extra
scan~5 kBtwo 180-sample history rings and a histogram
alarms~0.1 kBthe banner’s counts

Rebuilt and re-sent four times a second whether or not anything in them had moved. A client that had filtered its subscription down to nothing still pulled 4.35 MB a minute — a floor no amount of tag filtering could get under.

So a delta stream now gates those blocks by the same rule as the tags: absent means unchanged.

GET /api/stream?delta=1&blocks=delta
// a frame where a node dropped: the driver block, and nothing else
{"ts":1770000000250,"seq":41,"tags":{},"drivers":[{}]}
// the next frame: nothing happened, so nothing but the headline
{"ts":1770000000500,"seq":42,"scans":918274,"tags":{}}
  • drivers — hashed over everything an operator would call a change, and nothing that free-runs. A message counter climbing, an age ticking or the server’s own observation stamp must not put 13 kB on the wire, so they are excluded from the comparison (they still ride along whenever the block is sent). A driver adapter marks its own free-running readouts: DriverMetric.Volatile for a counter, DriverStatus.VolatileExtra for protocol-specific fields — by key, or by path, since nested churn is the common case. A 55-site Sparkplug host taught that one in production: each entry of its extra.nodes carried a last-message stamp and a sequence number that step on every message, so the block rode every frame anyway, and excluding the whole nodes key would have thrown away the roster the gate exists to watch. VolatileExtra: ["nodes.*.lastMsgMs"] excludes the two fields and keeps the rest (* matches any key or list element).

    The corollary is a rule for anyone writing a driver adapter: report the plant categorically. A flag, a count of sites, a moment (birthMs) — not an age rendered from the clock and not a message counter. A value that only refreshes when something else changes was never live to begin with, so pre-rendering it costs the whole block and buys nothing.

  • alarms — the engine already publishes a rev that bumps when an alarm moves and never otherwise. Gate on it. As a bonus the controller stops computing the summary on ticks nobody is owed one.

  • scan — there is no “unchanged”: every scan changes it. So it rides a cadence instead (server.Options{DiagnosticsInterval: …}, 3 s by default). The block is a history ring covering 180 samples — 18 s at a 100 ms scan — so a 3 s cadence delivers every sample a diagnostics page plots, just in batches. The live headline (scans, ts) rides every frame regardless.

A full frame carries all of them, which is what keeps “absent means unchanged” honest: no client is more than one resync (30 s) from a block it can vouch for. And the same enqueue discipline as the tags applies — a client’s record of which blocks it holds advances only when a frame is actually enqueued, so a dropped frame re-offers the block rather than losing it.

quality is deliberately not gated. An absent quality already means something on this protocol — “every tag is good” — and a field cannot mean both that and “unchanged”.

One minute of a 250 ms stream (240 frames) for a client subscribed to no tags at all, against the 55-node driver status above, with a resync every 30 s and one edge node dropping mid-minute (go test ./server/ -run XXX -bench FrameFloor -benchtime 1x):

BeforeAfter
bytes/minute4.3 MB0.15 MB

~28× less, and what is left is mostly the two resyncs and the scan cadence — both tunable, neither a floor.

The driver block is now sent seconds apart, which breaks anything the server pre-rendered from the clock: a “last publish 0.2s” frozen into a block sent 20 seconds ago reads as a plant going quiet. So a freshness readout travels as the moment itself:

{"kind":"sparkplug","name":"WRD/Host","asOfMs":1770000000000,
"metrics":[{"label":"last publish","atMs":1769999999800,"text":"0.2s"}]}
  • metrics[].atMs — the moment, epoch ms.
  • asOfMs — when the whole status was observed, stamped by the server.

A client renders the age as asOfMs − atMs, not against its own clock: the answer is then the same one the server would have rendered, and it does not creep upward between blocks. sinceMs (uptime) is different — an absolute start time, honestly measured against now. The kit’s DriverStatusCard does all of this; text is still sent for readers that predate atMs.

?blocks=delta is asked for, never assumed — the same argument as deltas themselves, one level down. An HMI built against the older protocol merges tags but not blocks, so gating them for it would blank its driver panel between changes: the same failure wearing the same disguise. /api/meta reports "blockDeltas": true on a controller that understands the parameter, and the HMI kit sends it whenever deltas are on (asking an older controller is harmless — it ignores the parameter and keeps sending every block).

A screen that draws forty points should pull forty points:

GET /api/stream?tags=RTU9_*,*_LIT_*
GET /api/state?tags=RTU9_*,*_LIT_*

Comma-separated glob patterns, matched with Go’s path.Match against the whole dotted tag name. The separator path.Match splits on is /, which no nautilus tag name contains, so a * spans a whole name: Tank* matches both Tank101 and Tank101.Level, and *.Level matches the member address form a screen binds with.

The filter applies to every frame including the first, and to the quality map alongside the tags — a filtered stream never carries quality for a tag it is not sending. It also applies to /api/state, so a screen’s initial load matches its subscription instead of pulling the whole plant to read forty points.

The reductions compose, and each is useful alone: filters help most when a screen is small, deltas when the plant is quiet, and the block gate when both have already done their work. Diagnostics, driver status and alarm counts are never filtered — a subscription narrows tags, not the controller’s own health — they are gated on change instead.

A pattern path.Match cannot compile is a 400, not a silent match-nothing; a screen bound to a typo should show an error, not an empty plant.

A tag store holds values. It does not, on its own, hold any statement about whether a value is worth believing — and an HMI that has to guess will guess with a heuristic like “is this number −9999?” or “has it moved lately?”, which goes wrong in both directions. A legitimately −9999-scaled analog reads as dead; a genuinely dead node whose last reading was plausible reads as live.

Frames now carry a quality map:

{
"ts": 1770000000000,
"tags": {"RTU9_WEL15_LIT_001": 4.31, "TempSP": 65},
"quality": {"RTU9_WEL15_LIT_001": "stale", "RTU4_FIT_002": "notConnected"}
}

Four values, because an operator screen makes exactly four distinctions:

ValueMeaningWhat a screen should do
goodcurrent value from a healthy sourceshow it
stalewas good, no longer refreshed — this is its last readingshow it, greyed, with its age
badthe source calls this reading untrustworthyshow the fault, not the number
notConnectedthe source has never deliveredshow “no data” — there may be no value at all

Two rules keep it affordable on a 10,000-tag controller:

  • Only non-good entries appear. An absent name is good. A healthy plant omits the field entirely, so quality costs a working controller zero bytes.
  • A name in quality need not be in tags. notConnected is exactly the source that has never delivered a value, so there is nothing to publish under it — and the binding shows the reason rather than an unexplained blank.

Two sources, in this order.

The driver, when it implements io.QualityReporter:

// Optional refinement on io.Driver. Return only the non-Good entries.
type QualityReporter interface {
Driver
Quality() map[string]Quality
}

It is the only thing that actually knows. A Sparkplug host driver knows which edge node died and which has never birthed; an EtherNet/IP driver knows which connection dropped. Whatever it says about a tag stands. Implementing it is never required — a driver that reports nothing behaves exactly as it did before quality existed. io.Memory implements it (SetQuality) so a simulation or a test can exercise the whole path without a field bus.

The runtime’s own derivation, for tags the driver said nothing about: when the last input read failed — or has not happened yet — every driver-bound input is stale. The scan ran on last-known values, which is what stale means, and it is a fact the runtime holds whether or not the driver reports anything. A plain io.Memory or a hand-written driver gets honest staleness for free.

A failed output write deliberately does not do this. An actuator refusing a command says nothing about how old the readings are, and marking every input stale over it would put a bad-quality badge on every screen in the plant every time one valve sulked.

GET /api/meta reports "quality": true when this controller can report quality at all. Check it before rendering a quality indicator, because the false case is invisible: an empty quality map looks exactly like a healthy plant, and a screen that cannot tell the two apart paints a confident green badge on a controller that has no idea. /api/meta also reports "deltas": true for ?delta=1 and ?tags= support, and "blockDeltas": true for ?blocks=delta.

RealtimeClient speaks all of this, and opts into deltas by default — the point being that nothing downstream notices:

const rt = new RealtimeClient<NautilusFrame>({
tags: ['RTU9_*'], // subscribe to a subset (optional)
delta: true // the default — tags AND the non-tag blocks
});
rt.start();
// frame.tags is always COMPLETE — the client merges deltas for you
rt.frame?.tags.RTU9_WEL15_LIT_001;
// and now a screen can stop guessing
rt.isGood('RTU9_WEL15_LIT_001'); // false when stale/bad/absent-source
rt.quality('RTU9_WEL15_LIT_001.CTL1HSP'); // 'stale' — resolves to the root tag

quality() resolves a dotted member path to its root tag: quality belongs to the delivery, and a UDT arrives from its source whole, so P101.Drive.Speed is exactly as trustworthy as P101 is. An exact entry for the full path still wins, for a controller that reports at member granularity.

Against a controller that predates any of this, the client falls back to plain pass-through automatically — frames arrive with no seq, and it publishes them untouched. Asking for deltas is never a compatibility risk.

frame.scan, frame.drivers and frame.alarms are complete on every published frame too: the client retains the last one it saw of each and puts it back, so no component has to know the controller stopped repeating itself.

The merge rules live in one small, dependency-free module (hmi/src/lib/delta.ts) with their own tests, precisely because they are the piece of the kit that can silently mislead an operator.