Serving OPC UA (preview)

An opcua: section in nautilus.yaml serves the controller’s tag store as an OPC UA address space. Any OPC UA client — a SCADA gateway, a historian, UAExpert — connects to the endpoint, browses the project folder under Objects, and reads or subscribes to the tags. Names, types, current values and each tag’s desc: and unit: arrive as data, not as configuration you re-enter on the client side.

opcua:
endpoint: opc.tcp://0.0.0.0:4840 # default opc.tcp://localhost:4840

naut run (and a built binary) starts the server alongside the scan loop; the section’s presence turns it on (opcua: {} serves on the default), and endpoint is the only setting. It defaults to the loopback interface — localhost listens on 127.0.0.1 — so putting a controller on the network is a line you write: opc.tcp://0.0.0.0:4840 listens on every interface. naut check refuses an endpoint that is not opc.tcp://host:port (a bare host:port is read as opc.tcp://host:port).

An OPC UA client finds an endpoint by its exact URL, so the server advertises one per name it answers to: the host you wrote, every interface address when you wrote 0.0.0.0, the machine’s host name, and loopback. A client may dial any of them. One that asks about a URL the server never heard of (a NAT address, a DNS alias) is given the whole list by GetEndpoints, but the session itself has to be opened through one of the advertised names: there is no way yet to advertise a name the host does not know about (#430).

The server is read-only: a write is answered Bad_UserAccessDenied, never silently dropped. See Security for why, and what comes next.

Under Objects there is one folder named after the project. Inside it, one node per tag:

  • A scalar tag (BOOL, INT, REAL, STRING, TIME, an enumeration) is a Variable.
  • A UDT tag is an Object whose members are child nodes — nested UDTs nest. (A function-block instance is program state, not a tag, so it has no node.)
  • An array of scalars is a Variable holding an OPC UA array (ValueRank 1, ArrayDimensions the declared length).
  • An array of UDTs is an Object with one child per element, indexed from the declared lower bound: Pumps[1], Pumps[2].
  • A two-dimensional array (ARRAY[0..1, 0..2] OF INT) is an Object of one-dimensional rows, Grid[0], Grid[1], each a Variable holding an array.

Node ids are string ids in the tag store’s own address form, in the project’s namespace — index 1, the entry after the standard http://opcfoundation.org/UA/ in the server’s NamespaceArray, with the URI urn:joyautomation:nautilus:<project> — so a client that already knows a nautilus address can write the node id down without browsing for it:

ns=1;s=Level a tag
ns=1;s=P101.Drive.Speed a member of a UDT tag
ns=1;s=Levels[2] an element of an array of UDTs

Tag names are IEC identifiers, so ns=1;s=level resolves to Level. A tag’s desc: and unit: from the tag model become the node’s Description — Wet well level [ft].

A Read of an array honours its IndexRange: 2 is one element, 1:3 a slice, counted from 0. A STRING is an array of characters, so 0:3 on one is its first four, and an array of strings takes a second dimension (1,0 is the first character of the second string). A range that starts past the end of the value, or a range on a number or a boolean, is Bad_IndexRangeNoData; one that starts inside it and runs past the end is what there is, so 0:9 on four elements is all four, and in an array of strings a string too short for the range is "". A monitored item’s IndexRange means the same: the item hears its slice, and only when the slice changes. One Read may name up to 10 000 nodes — the MaxNodesPerRead the Server object advertises is the limit the server enforces, with Bad_TooManyOperations past it — so a project of a few thousand tags is still one call. A Browse lists each reference once, the standard Server object’s included.

The tag store holds every integer as 64 bits and every real as a double, but a DINT is still a DINT: each node’s DataType is the type the tag was declared as.

IEC typeOPC UA DataType
BOOLBoolean
SINT / USINT, BYTESByte / Byte
INT / UINT, WORDInt16 / UInt16
DINT / UDINT, DWORDInt32 / UInt32
LINT / ULINT, LWORDInt64 / UInt64
an enumerationInt32 (the member’s value)
REAL, LREALDouble
TIMEDuration (a Double of milliseconds)
STRINGString
ARRAY [..] OF a scalaran array of the element’s type

An integer that does not fit its declared width — which a declared variable never produces — is sent as Int64 rather than wrapped.

Every value carries the tag’s quality as its OPC UA status code, so a client that only checks the severity bit treats a dead reading the way an HMI treats a bad binding:

QualityStatus
goodGood
stale — the source stopped refreshing itUncertain_LastUsableValue
bad — the source reports it untrustworthyBad_DeviceFailure
not connected — never deliveredBad_NotConnected

A member of a UDT is exactly as trustworthy as its tag. SourceTimestamp is the time the tag’s current value was first seen — the server’s start, for a value nothing has changed since — and moves only when the value does: a member of a UDT keeps its own timestamp while a sibling member changes. ServerTimestamp is the time of the read.

Three limits of the current server, found by its black-box runs and tracked as issues: a local-I/O input (plcnext, optommp) that has never been delivered has no node until its first value arrives, and a client that browsed early must browse again (#420). A protocol driver’s input (Modbus, EtherNet/IP, Sparkplug host, the IT pollers) is seeded with its init: or zero (see Inputs from a device that is down), so it has a node from the start and reads Bad_NotConnected until the device answers; and a change of quality alone, with the value unchanged, is visible to a Read but not yet pushed to a subscription (#419); and a subscription’s interval, counts and items are fixed once created, and it cannot be paused or moved to a new session (ModifySubscription answers with the values it has; ModifyMonitoredItems, SetPublishingMode and TransferSubscriptions, like TranslateBrowsePathsToNodeIds and Call, answer Bad_ServiceUnsupported; #431).

A client may create subscriptions and monitor any Variable. The server never polls a copy of the tag store: every 100 ms it asks the store which tags changed since the last sweep — one integer compare per tag, using the same write generations the HTTP stream uses — and notifies only the monitored items whose value or status actually changed; a member of a UDT is quiet while its siblings move. A subscriber hears of a change within one sweep plus its own publishing interval; MinimumSamplingInterval reports the sweep; a requested sampling interval is revised to the nearest multiple of it, and the item is sampled at that rate. A requested publishing interval is revised the same way — 0 asks for the fastest and is granted the sweep; nothing slower than an hour is granted — rather than booked as asked, and a ModifySubscription that follows (asyncua sends one to realign its counts) is answered with the values the subscription has. SetMonitoringMode means what it answers: a Disabled or Sampling item is silent until it is Reporting again, and then hears the current value first; an item created Disabled is silent from the start.

An item that cannot be monitored — a node id that is not a node, or a Value on an Object or the folder — is refused when it is created, with the code a Read of it gives (Bad_NodeIdUnknown, Bad_AttributeIdInvalid), not created and left to fail inside a notification.

The server offers the None security policy with anonymous sessions, and every node is read-only (AccessLevel is CurrentRead) — the standard Server object and its variables included, so no session can rewrite the NamespaceArray or ServerStatus other clients rely on. That is the combination that is safe to offer without a certificate store: anonymous clients can look, nobody can write.

Writes are planned as a follow-up, and will land only on a secure channel (Basic256Sha256) from a client certificate the controller trusts, going through the same path as POST /api/tags — so the write token, forcing rules and member-write checks the HTTP API applies hold for OPC UA too. Until then, a controller that must take setpoints from a SCADA host should take them over Sparkplug or the HTTP API.

The dashboard’s driver cards and GET /api/drivers carry an opcua-server row: the endpoint, whether it is listening, and how many subscriptions and monitored items clients hold. A port already in use is reported there and on stderr at start (continuing without it); the controller runs regardless.