IT hardware (SNMP, Redfish, node_exporter)

Three drivers: types turn IT hardware into the same kind of tag a pump is: snmp for switches, PDUs and UPSes, redfish for server BMCs, and prometheus for hosts scraped straight from node_exporter. They deliver one shared UDT set, so a switch port, a fan or a PSU is bound, alarmed, trended, published and rendered in 3D exactly like plant equipment — the brief is docs/design/it-drivers.md, and §2 there is the contract.

UDTWhat it isAlarm member
Servera machine: power, health, temps, CPU/memory, fan/PSU countsFault, Warning
Fan, PSU, TempSensorchildren of a server or a switchFault; High, HighHigh
Switch, SwitchPorta managed switch and each interface: link, speed, rates, errors, PoEFault; Down (enabled, no link)
PDU, PDUOutlet, UPSrack powerOverload; OnBattery, LowBattery, BatteryFault

Instances are flat, not arrays — SW1_Port03 : SwitchPort, NODE1_Fan2 : Fan, NODE1_Temp_Inlet : TempSensor — because that is what alarm rules, Sparkplug Templates and a scene file address by name.

Terminal window
# a switch over SNMPv3 (v2c: --community-env SNMP_SW1_COMMUNITY instead)
naut snmp import --tag SW1 --host 192.168.1.2 --version 3 --user mon --auth sha256 --priv aes128
# a BMC (self-signed certificate: --insecure, or --ca-file)
naut redfish import --tag NODE1 --host https://bmc1 --user mon --password-env BMC_NODE1_PASSWORD --insecure
# a host running node_exporter
naut prometheus import --tag HOST1 --url http://host1:9100/metrics

A live Prometheus import needs the whole scrape: one that does not finish within --timeout (default 5 s) fails rather than generating a manifest from the part that arrived.

Each importer writes <proto>_manifest.yaml, tags/<proto>.yaml and hw_types.st — generated, never hand-edited, byte-identical on re-run. All three write the same hw_types.st, so a project with a switch and a host keeps one types file. The manifest is explicit — every member of every tag names its OID, its Redfish resource and path, or its metric selector — so a reviewer sees exactly what will be polled, and a device the profiles have never met is handled by editing the manifest, not the driver.

drivers:
- type: snmp
manifest: snmp_manifest.yaml
scan-rate: 5s # a poll INTERVAL, in seconds
scan-classes: { slow: 60s }
tag-classes: { slow: ["*.Name", "*.Alias", "*.Model", "*.Serial"] }
- type: redfish
manifest: redfish_manifest.yaml
scan-rate: 10s # BMCs rate-limit; 10 s is a safe floor
- type: prometheus
manifest: prometheus_manifest.yaml
scan-rate: 15s
tag-files: [tags/snmp.yaml, tags/redfish.yaml, tags/prometheus.yaml]

manifest: is the only required key. New never dials: naut check and naut build validate every binding offline, with no device in sight.

Never in the manifest, the tag file, a log line or an error. A source names the variable (community-env: SNMP_SW1_COMMUNITY, auth-env, priv-env, password-env) or the file (community-file, password-file, for a mounted Secret) the driver reads where it runs. naut check warns when a named variable is unset — a warning, never an error, because check runs on laptops that have none of the controller’s secrets. SNMPv3 with SHA-256 and AES-128 is what a managed switch should be on; MD5 and DES are accepted with a warning.

  • <id>__Online is true while the source answered within stale-after (default three intervals of the fastest scan class it polls). A device that stops answering keeps its last values, marked Stale — never a silent zero — so interlock on __Online before trusting a device’s tags, and use it as the alarm rules’ enable: so a dark device’s alarms are Suppressed instead of frozen lit. An unbound Online member on Server, Switch, PDU and UPS mirrors the same verdict. <id>__LastPollMs is the poll clock.
  • Rates: InBps, OutBps, ErrorRate are per-second rates of wire counters, with 32-bit wrap and 64-bit reset handled (a step backwards on a 64-bit counter is a reboot, not a wrap). A 32-bit counter can reset too: a step backwards that would mean more than half its range in one interval is read as a reset, and an SNMP source’s sysUpTime going backwards marks every rate across the restart as a reset whatever the counter did. A reset delivers no rate for that interval; the rate before it is kept. Rates read 0 for exactly one interval after a source connects.
  • Bad, per tag: a refused OID, a 404 resource or a metric the exporter no longer carries marks that tag Bad and leaves its siblings Good. A transport failure (timeout, refused, bad credentials) climbs a backoff ladder from 1 s to 60 s and shows on /api/drivers with the reason — a wrong SNMPv3 auth pass phrase reads as authentication failed — wrong auth pass phrase or protocol for user …, and a wrong priv pass phrase as authentication succeeded but privacy failed, not as a timeout.
alarms:
site-from: "^([A-Za-z0-9]+?)(?:_|$)" # SW1_Port03 → SW1, NODE1_Fan2 → NODE1, SW1 → SW1
rules:
- { match: { type: SwitchPort, member: Down }, priority: medium, on-delay: 15s, enable: "{site}__Online" }
- { match: { type: Fan, member: Fault }, priority: high, on-delay: 30s, enable: "{site}__Online" }
- { match: { type: PSU, member: Fault }, priority: high, enable: "{site}__Online" }
- { match: { type: TempSensor, member: HighHigh }, priority: critical, on-delay: 10s, enable: "{site}__Online" }
- { match: { type: UPS, member: OnBattery },priority: high, enable: "{site}__Online" }

One rule per (type, member) covers every port, fan and sensor on every device — now, and after the next import adds a device.

The importers generate no writable binding. A PDU outlet command or a server power command is added by hand, in a reviewed diff, as its own scalar output tag bound to the member it acts on:

writes:
- { name: PDU1_Outlet03_Cmd, tag: PDU1_Outlet03, member: On, oid: 1.3.6.1.4.1.3808..., set: { true: 1, false: 2 } }
- { name: NODE1_PowerCmd, tag: NODE1, member: PowerOn, target: /redfish/v1/Systems/1/Actions/ComputerSystem.Reset }

SNMP has no boolean type, so a BOOL command over SNMP must say what each value writes: set: maps true and false to the INTEGERs the object takes (TruthValue is { true: 1, false: 2 }; vendor MIBs vary), and naut check refuses a BOOL write without it rather than send 0 for false.

NODE1_PowerCmd is an INT: 0 none, 1 on, 2 graceful shutdown, 3 force off, 4 restart — posted once on the change to a non-zero value; the program returns it to 0. Every command goes through the runtime’s existing gates: the leader only, the write token, the HMI’s confirm dialog. The first value seen after a start is a baseline that is never written, so init: false on an outlet command cannot switch the outlet off at boot. Automatic power actions from control logic are deliberately out of scope: a controller that can power-cycle the node it runs on is a loop, and fencing belongs to the cluster’s own tooling.

Terminal window
naut snmp browse --host 192.168.1.2 --record switch.snmpwalk # then import --walk
naut redfish browse --host https://bmc1 --record bmc1/ # then import --mockup
naut prometheus browse --url http://host1:9100/metrics --record host1.prom
naut snmp serve --walk switch.snmpwalk --ramp & # a v2c agent on 127.0.0.1:1161
naut redfish serve --mockup bmc1/ & # a BMC on 127.0.0.1:8000
naut prometheus serve --file host1.prom --ramp & # an exporter on 127.0.0.1:9100

An import from a recording gives the same bytes as from the live device, so the recording is the fixture the bench, the golden tests and CI all share. A Redfish recording carries serial numbers and addresses: review it before committing. examples/it-rack is the whole story runnable on a laptop — a switch and a host, rules, rollups, an acceptance suite in virtual time — and the same project pointed at real devices.

  • snmp — IF-MIB/ifXTable for ports (64-bit counters, falling back to 32-bit), ENTITY-MIB for the chassis, ENTITY-SENSOR-MIB and POWER-ETHERNET-MIB where present; RFC 1628 UPS-MIB and CyberPower’s CPS-MIB for the PDU and UPS profiles (written from the published MIBs, marked unverified until a device confirms them). One GetBulk walk per table column per poll, not one Get per port. v2c and v3.
  • redfish — both generations: legacy Chassis/{id}/Thermal and Power, and 2021+ ThermalSubsystem, PowerSubsystem and Sensors; sessions with basic-auth fallback; paths select array members by MemberId or Name, never by position, because BMCs reorder arrays across firmware.
  • prometheus — the exposition text format from node_exporter (pinned to a release; the profile reports a bound metric the scrape no longer carries); CpuPct, MemPct, RootDiskPct and uptime as small expressions over named selectors; fans and temperature sensors from hwmon with their own thresholds. Scrapes the exporter directly — no Prometheus server needed.