Read one Modbus register, with no hardware
Modbus TCP is the protocol most field devices speak. In this lesson a
controller reads a tank level transmitter, and you need no hardware: a
simulated device runs on your computer. It takes about ten minutes. You need
naut (install) and a project
(your first controller).
The idea
Section titled “The idea”A Modbus device is a numbered list of registers. The datasheet says what is at each number, how to read it (a 16-bit integer, a 32-bit float), and how to scale it (the level is sent as tenths of a percent). nautilus keeps that knowledge in one file you write by hand, the device map, and generates everything else from it. You never edit the generated files.
1. Start a project and write the device map
Section titled “1. Start a project and write the device map”naut new tank --template minimalcd tankCreate devices.yaml in the project folder. This says: a type of device (what the datasheet
tells you), and an instance of it (where this one is):
devices: level-transmitter: description: Tank level transmitter registers: - {tag: Level, address: 0, format: int16, scale: 0.1, unit: "%", desc: tank level} - {tag: Flow, address: 1, format: float32, unit: "m3/h", desc: inlet flow}instances: - {id: LT1, type: level-transmitter, host: 127.0.0.1, port: 15020, unit-id: 1, desc: the bench simulator}address is the register number from the datasheet counted from 0. The
format and scale turn the raw register into the number you want: the
raw 425 in register 0 is 42.5 after scale: 0.1. unit-id picks which
device answers when several share one address (a gateway). host and port
are where it lives; 502 is the Modbus default, and here we use a free port
on your own computer.
2. Generate the bindings
Section titled “2. Generate the bindings”naut modbus import --map devices.yamlwrote modbus_manifest.yaml (1 sources, 2 tag bindings)wrote tags/modbus.yaml — compose it with `tag-files: [tags/modbus.yaml]`Two files appeared, and both start with a comment saying not to edit them:
modbus_manifest.yaml is how to poll the device, and tags/modbus.yaml
declares the tags. The tags are named with the instance id in front,
LT1_Level and LT1_Flow, so two devices of one type do not clash. Use
those names in your program. Open tags/modbus.yaml and there are two more:
- { name: LT1__Online, role: input, type: BOOL, desc: "source LT1 answering — interlock on this" }- { name: LT1__Outages, role: input, type: DINT, desc: "times LT1__Online has fallen since the driver started" }You did not ask for these. For every device the controller adds an
__Online tag, true while the device is answering, and an __Outages
counter of how many times it has stopped. Step 3 uses the first.
3. Point the project at the device
Section titled “3. Point the project at the device”Replace nautilus.yaml with:
name: tank
server: addr: "localhost:8080"
tasks: - program: program.st scan: 100ms
tag-files: [tags/modbus.yaml]
tags: - { name: HighLevel, role: output, type: BOOL, init: false, desc: Level above 80 % } - { name: DeviceUp, role: output, type: BOOL, init: false, desc: The transmitter is answering }
driver: type: modbus manifest: modbus_manifest.yaml scan-rate: 1sdriver: modbus replaces the memory loopback, and tag-files brings in
the generated tags. HighLevel and DeviceUp are output tags: tags the program writes.
Replace program.st with two lines of logic that use device tags, and delete
the scaffold’s tank_test.yaml (it tests the old program):
PROGRAM TankHighLevel := LT1__Online AND LT1_Level > 80.0;DeviceUp := LT1__Online;END_PROGRAMHighLevel only turns on while the device is answering: a level that is stale
because the transmitter is down should not raise an alarm, and a program should
say so.
naut checknaut check builds the read plan from the manifest without any device
running, and should say 0 with errors.
4. Start the simulated device
Section titled “4. Start the simulated device”A bench device ships inside naut. It answers for the manifest you
generated, with the values you give it. In seed.json, in the project folder, give it values in
real units (the scaling is undone for you):
{"LT1_Level": 42.5, "LT1_Flow": 3.25}In a second terminal, in the project folder:
naut modbus serve --manifest modbus_manifest.yaml --values seed.json --listen 127.0.0.1:15020Check what is on the wire with the commissioning tool, which reads a range of registers and shows each one in every format at once:
naut modbus browse --host 127.0.0.1 --port 15020 --unit 1 --from 0 --count 3addr raw uint16 int16 int32 uint32 float32 float640 0x01A9 425 425 27869264 27869264 6.21731e-381 0x4050 16464 16464 1078984704 1078984704 3.252 0x0000 0 0Register 0 is 425 as an int16 and register 1 is 3.25 as a float32:
the formats in the device map. A 32-bit value spans two registers, so the
float32 in row 1 is only shown once register 2 is read too: that is why the
command asks for three. On a real device this table is how you find
out which format a register really is.
5. Run the controller against it
Section titled “5. Run the controller against it”naut runYou should see modbus: connected and the dashboard on
http://localhost:8080 (if that port is already in use, naut run says so and
prints the address it moved to; use that one). The tags now come from the
device:
curl -s localhost:8080/api/state | jq -c .tags(jq only tidies the output; without it, plain curl prints the whole state.)
{"DeviceUp":true,"HighLevel":false,"LT1_Flow":3.25,"LT1_Level":42.5,"LT1__Online":true,"LT1__Outages":0}HighLevel is false because 42.5 is below 80, and DeviceUp is true because
the device is answering.
Is the device there?
Section titled “Is the device there?”Stop the simulator (Ctrl+C in its terminal) and read the tags again after a few seconds:
{"DeviceUp":false,"HighLevel":false,"LT1_Flow":3.25,"LT1_Level":42.5,"LT1__Online":false,"LT1__Outages":1}LT1__Online has gone false and LT1__Outages has counted the outage. The
level and flow still show their last values, so the logic must not trust them
on their own: that is why HighLevel asked for LT1__Online first. The
dashboard’s driver card shows an error, and /api/state gains a quality
entry for the two readings, LT1_Level and LT1_Flow, as stale. A device that never answers at all
reports notConnected.
Start the simulator again. The controller reconnects by itself, with no restart, but not at once: after a failed attempt the driver waits 1 second, then 2, 4 and 8 before trying again, so read the tags again after up to 20 seconds. The controller’s log shows each try.
{"DeviceUp":true,"HighLevel":false,"LT1_Flow":3.25,"LT1_Level":42.5,"LT1__Online":true,"LT1__Outages":1}LT1__Online is true again; LT1__Outages stays at 1, a count of the times it
fell since the driver started. (The quality entries go away: a good tag
carries none.)
To use a real device, change host: (and port:, usually 502) in the
instance and run the import again; nothing else changes. The Modbus
guide covers word and byte order, writes, and keep-alive
rewrites.