Studio 5000 (RSLogix) ladder is relay logic with a vendor instruction set. nautilus ladder is the IEC 61131-3 grammar written as text, so most Logix habits carry over one for one and a few have a different shape. This page is the map. Read the ladder page for the full grammar.

Rows marked declined are not coming; the section after the tables says why and what to do instead, and the same list is on Not supported, by design.

Logixnautilus rung textIn the diagram
XIC TagTagNO contact, Tag above --\ \--
XIO Tag/TagNC contact, a slash through the contact
OTE Tag( Tag )output coil at the right rail
OTL Tag( S Tag )coil marked S
OTU Tag( R Tag )coil marked R
OSR (output)( P Tag )coil marked P: Tag is TRUE for one scan when the rung condition rises
OSF (output)( N Tag )coil marked N: one scan when the rung condition falls
ONS+Tag as a contact, or ( P Pulse ) then Pulse on the next rungthe pulse coil draws as P; an edge contact (+Tag) is not drawn as a contact yet (#212) and has no palette item (#213), so write it in the text
Branch[ a | b ]parallel legs, nested to any depth

ONS is a one-shot at a position in the rung. nautilus has two spellings. If the thing that should fire once is a single tag, put +Tag where the ONS would be. If it is a whole rung condition, end that rung in a pulse coil and use the pulse as the contact on the next rung. There are no storage bits to declare: the compiler generates the edge instance and keeps its state stable across unrelated edits. -Tag is the falling-edge contact.

A timer or counter is a block instance in the rung. Power from the rung drives its input pin and leaves from its output pin; every other pin is bound by name in the parentheses. PT is a TIME, written T#5S, not a millisecond DINT.

LogixnautilusNotes
TON t PRE 5000t:TON(PT := T#5S)declare t : TON; under VAR
t.DNt.Qreadable anywhere, including as a contact
t.TTthe rung’s own condition, and /t.Qthere is no separate timing bit
t.ENthe rung’s own conditionpower into the block is the enable
t.ACCt.ETa TIME; compare with GE(t.ET, T#2S)
t.PREPTbound at the call, or any TIME expression
TOF tt:TOF(PT := T#5S)Q stays TRUE for PT after IN drops
RTO tno retentive timer blocksee below
RES t (timer)t:TONR(PT := T#5S, Reset := Clear)needs dialect: logix in nautilus.yaml; clears ET and Q while Reset is TRUE
CTU c PRE 10c:CTU(PV := 10, R := ResetC)rung power is CU; counts rising edges
c.DNc.Q
c.ACCc.CV
CTD cc:CTD(PV := 10, LD := Load)rung power is CD; Q when CV <= 0
RES c (counter)the R pin: c:CTU(PV := 10, R := ResetC)the reset is a pin bound to a tag, not a rung instruction

Two semantic differences are worth knowing before you port logic:

  • CTD is the IEC block. It counts down from PV (loaded by LD) and Q means CV <= 0. A Logix CTD counts from ACC and its .DN compares to the preset the other way round, so re-derive the done condition rather than translating the bit.
  • There is no RTO block. A retentive timer is an accumulator you write yourself: in a rung with an assignment, Run { Hours := Hours + ScanDt }, or in an ST block, and cleared by a reset rung.
LogixnautilusNotes
EQU A BEQ(A, B)a function contact; /EQ(A, B) negates
NEQ, GRT, GEQ, LES, LEQNE, GT, GE, LT, LEthe diagram captions follow the IEC names
LIM Low Test HighGE(Test, Low) LE(Test, High)two contacts in series. The IEC LIMIT(MN, IN, MX) clamps a value, it does not test one, so it is the wrong spelling for this
MOV Src Dest{ Dest := Src }made while the rung has power; power passes through
CPT Dest Expr{ Dest := Expr }any IEC expression, evaluated every scan
ADD, SUB, MUL, DIV, MOD, NEG, ABS{ Sum := A + B } and the matching operatorsinside an assignment, or as a function in a comparison
bit of a DINT (Status.3)Status.3a BOOL, readable and assignable; bit 0 is least significant

Ladder power is boolean, so a numeric function is not a contact on its own. ADD(A, B) goes inside a comparison, GE(ADD(Base, Bias), Limit), or into an assignment.

The assignment is one element in the rung’s text, { Dest := Expr }, with power passing straight through. Longer math can live in an ST program that shares the tag store with the ladder one; that is the pattern the demo project uses.

LogixnautilusIn the diagram
JSR / SBR / RETa FUNCTION_BLOCK calla block in the rung, pins down both sides
AOIFUNCTION_BLOCK in lib/*.ldthe same block, opened by double-click
AOI parametersVAR_INPUT, VAR_OUTPUT, VAR_IN_OUTpins
AOI backing tagthe instance, m101 : MotorStarter;the instance name above the block
m101.Memberm101.Pinreadable anywhere as a contact or an operand
local tagsVARper-instance retained state

A JSR shares the controller’s tags with its caller. A block has pins and its own state per instance, so two pumps are two instances of one block with no shared tags to collide. This is what an AOI already was; port a routine as a block and pass what it needs as pins. See Function blocks, libraries, and tasks.

Logixnautilus
controller-scope tagan entry in nautilus.yaml or tags/*.yaml, in scope in every program as it is
a tag’s Data Typethe tag’s type: — BOOL, DINT, REAL, TIME, a UDT, an ARRAY
program-scope tagVAR in the program
alias tag, rack pointthe tag’s alias: field, dialect: logix
task, programtasks: in nautilus.yaml, one program file per task
UDTTYPE … STRUCT … END_STRUCT
tag descriptionthe tag’s desc: (the diagram does not show it on the element yet, #216)

Manifest tags are visible in every program without a declaration, as controller-scope tags are in every Logix routine (#177, #210); the ladder editor no longer offers to declare one. VAR_EXTERNAL stays legal, and must agree with the tag’s type:. A function block (the AOI) does not see tags implicitly: like an AOI, it takes what it needs as parameters, or names a tag in its own VAR_EXTERNAL.

LogixAnswer
JMP / LBLnot supported. Put the skipped logic in a function block and call it conditionally, or gate its rungs on a shared condition
MCRnot supported. Use the function-block pattern below
GSV / SSVdialect: logix (planned): controller and module attributes as blocks. Not available yet
COP / CPYdialect: logix (planned). For a UDT, assign the structure or its members in ST
AFI, NOPnothing to translate; they do nothing

Rungs run top to bottom every scan, and that is the whole control-flow model. A jump that skips rungs is the same as the skipped rungs having an enabling condition, and a block is the way to say that.

A master control relay zone de-energizes every non-retentive output between two MCR rungs when the zone is off. The function-block pattern is the same behavior stated once, in a unit with its own pins. Put the zone’s rungs in a FUNCTION_BLOCK with an Enable input, and gate the outputs on it:

FUNCTION_BLOCK Zone1
VAR_INPUT Enable : BOOL; Start : BOOL; Stop : BOOL; END_VAR
VAR_OUTPUT Run : BOOL; END_VAR
LD
RUNG run
[ Start | Run ] /Stop Enable ( Run )
END_LD
END_FUNCTION_BLOCK

Call it from the main program with z1:Zone1(Enable := ZoneOn, Start := …). Every output inside is dead while Enable is FALSE, as MCR makes it. Latched outputs that MCR would not clear are written explicitly, which is the safer thing to read in review.

  • Editing: FB… in the ladder palette inserts the block call that you would have built from the instruction toolbar. In the editor lists every gesture.
  • Importing: a Rockwell .L5X export opens as ladder with no Studio 5000 installed; see the Allen-Bradley Logix guide.
  • Starting from ladder: choose nautilus: Create Project…, then Minimal, then Ladder Diagram.