Your own function block

A program that controls two pumps should not contain two copies of the same logic. In IEC 61131-3 the unit of reuse is the function block: logic with its own memory, which you use as many times as you need. You have used built-in ones already (TON, CTU); this lesson writes your own. About ten minutes.

A function block is declared once, and each use is an instance with its own variables. Two TONs do not share an elapsed time; two of your blocks will not share their state either. Put the block in a library file, a file that holds only declarations, in the project’s folder (or in a lib/ folder). naut compiles library files ahead of the programs, so the block is in scope everywhere without an import.

Make a project (naut new pumps --template minimal) and replace its tags in nautilus.yaml with two start buttons, two stop buttons and two run outputs:

tags:
- { name: Start1, role: setpoint, type: BOOL, init: false, desc: Pump 1 start }
- { name: Stop1, role: setpoint, type: BOOL, init: false, desc: Pump 1 stop }
- { name: Run1, role: output, type: BOOL, init: false, desc: Pump 1 run }
- { name: Start2, role: setpoint, type: BOOL, init: false, desc: Pump 2 start }
- { name: Stop2, role: setpoint, type: BOOL, init: false, desc: Pump 2 stop }
- { name: Run2, role: output, type: BOOL, init: false, desc: Pump 2 run }

Create blocks.st beside nautilus.yaml:

FUNCTION_BLOCK MotorStarter
VAR_INPUT Start : BOOL; Stop : BOOL; END_VAR
VAR_OUTPUT Run : BOOL; END_VAR
(* seal-in: Start or already running, and Stop not pressed *)
Run := (Start OR Run) AND NOT Stop;
END_FUNCTION_BLOCK
  • VAR_INPUT are the values the caller hands in; VAR_OUTPUT are what it gets back.
  • Run is read on the right of its own assignment: the block remembers it from one scan to the next, which is what makes it a seal-in. Variables in a block keep their value between calls, per instance.

Replace program.st:

PROGRAM Pumps
VAR
pump1 : MotorStarter;
pump2 : MotorStarter;
END_VAR
pump1(Start := Start1, Stop := Stop1);
Run1 := pump1.Run;
pump2(Start := Start2, Stop := Stop2);
Run2 := pump2.Run;
END_PROGRAM

pump1 : MotorStarter; makes an instance. pump1(Start := …, Stop := …) calls it once per scan, passing its inputs, and pump1.Run reads its output.

Terminal window
naut check
naut check: 2 file(s), 0 with errors

The test that matters for a block is that two instances do not interfere. In pumps_test.yaml:

tests:
- name: each pump seals in on its own
steps:
- given: { Start1: true }
scans: 2
- given: { Start1: false }
scans: 2
expect: { Run1: true, Run2: false }
- name: stopping one pump leaves the other running
steps:
- given: { Start1: true, Start2: true }
scans: 2
- given: { Start1: false, Start2: false }
scans: 2
- given: { Stop1: true }
scans: 2
expect: { Run1: false, Run2: true }
Terminal window
naut test
pumps_test.yaml
ok each pump seals in on its own
ok stopping one pump leaves the other running
2 tests, 2 passed, 0 failed

A third pump is one more VAR line and one more call, not another copy of the logic. Fix the logic once in blocks.st and every pump has the fix.

A function is a block without memory: it computes a result from its inputs and keeps nothing (LIMIT, MAX and your own). Use a function for a calculation and a block for anything that must remember. A block can also be written in ladder or function block diagram, and used from any language. The function blocks and tasks guide covers both, and where library files live.

Two tasks, two scan rates.

nautilus is free and open source (Apache 2.0), built by Joy Automation. For implementation or support on your site, see Joy Automation services. Privacy.