IO-Link devices on a master (preview)

An IO-Link master is an ordinary OPC UA device (see Reading OPC UA); the sensor on each of its ports is described by an IODD, an XML file its maker ships. nautilus reads the IODD so that nobody writes a decode by hand, checks that the right sensor is on the port, and reaches the sensor’s parameters.

Import the IODD into the project, then name it on the master’s row:

naut iolink import acme-level100-20261118-IODD1.1.xml
devices:
- name: M
profile: sick-sig300
endpoint: 10.0.0.30
ports:
1: { name: LEVEL1, iodd: acme-level100-20261118-IODD1.1.xml }

LEVEL1 is a struct tag: one member per process data item, typed by the IODD (a scaled integer is a REAL), with PdValid when the master says whether its image is valid. The IODD copy in iodd/ is the pin: an upgrade of nautilus never changes how a deployed controller decodes a port. Two more tags come with it, LEVEL1__Identity and LEVEL1__IdentityFault, and, for a sensor with process data out, a command tag per item (LEVEL1_Mode) and LEVEL1__Rearm.

Identity, and what a wrong sensor does to outputs

Section titled “Identity, and what a wrong sensor does to outputs”

The master reports each device’s vendor and device id. When they are not the IODD’s, LEVEL1__Identity says WrongDevice or NoDevice and the sensor’s bytes are not decoded. LEVEL1__IdentityFault is true and, when the project has alarms:, a high-priority alarm is raised.

A master keeps the last process data out it was given and sends it to whatever is on the port, so not writing is not safe. A port with process data out is therefore armed:

  • the first time its identity is Ok, at a power-up or a takeover, it is armed with no action, and sends your program’s current values;
  • when the device stops being the right one while running (a swap), nothing is sent, and the master’s own “PDO valid” flag is driven false where it has one, so the device falls back to its fail-safe values;
  • when the right device is back the port stays quiet, reads AwaitingRearm, and keeps the alarm active, until LEVEL1__Rearm is pulsed (false, then true). The pulse sends the values your program holds then, never the ones from before the swap, and is refused while the device is not the right one.

A master whose profile has no “valid” flag cannot drop it: a wrong device on its port is sent the master’s last process data out until you stop it, and naut devices show and naut check say so for that master.

A sensor’s parameters (a setpoint, a tag, a window) are read and written through the master by ISDU. They go through the running controller’s API, never to the master directly, so a write is authorized and journalled:

naut iolink param list --host plc1 LEVEL1
naut iolink param get --host plc1 LEVEL1 V_Setpoint
naut iolink param set --host plc1 LEVEL1 V_Setpoint 500
  • A read works whichever device is on the port and says which; one taken from a device that is not the one expected says so.
  • A write needs the config permission (or, without an auth: block, the controller’s write credential, NAUTILUS_TOKEN), is journalled as param.write <port device>/<variable> with the value held before and after, and is refused unless the device on the port is the expected one, so a parameter is not sent to a device the controller knows is wrong (a swap during the write is covered below).
  • A value is checked against the IODD (access rights, range, type) before anything is sent.
  • If the device on the port changes while a write is under way, or the write was sent and the master did not answer (a timeout, a lost connection), the answer is outcome uncertain (502, and the journal records it as unknown), not success and not failure: the device may have taken it. naut iolink param set says so, does not retry, and tells you to check with get. The identity check is as fresh as the master’s last scan of its ids, so the window is narrowed, not closed.
  • One ISDU call at a time per port: a second request (read or write) while one is in flight is refused with 429 and Retry-After, with nothing sent to the master, so parameter reads cannot flood it. With an auth: block, a read needs the read permission.
  • Over a master that carries a parameter as hex text (the ifm masters), a parameter over 32 octets cannot be read or written.

A parameter lives on the sensor, so a new leader has nothing to replay: a parameter write is leader-only and has no entry in the operator-intent log. The audit journal is its record. A standby refuses a write (503), as it does for other writes; reads are answered by whichever controller holds the master’s session.