A Modbus datasheet is a table of registers in the vendor’s words. This lesson translates each word into the device map you wrote in the last lesson, including the one that catches everybody: “low word first”. It takes about ten minutes, with no hardware, using the bench device that ships inside naut.

Here is the register table of a flow meter, as a vendor might print it:

AddressTypeMeaningNotes
40001HoldingFlow rate, m³/h32-bit float, low word first
40003HoldingTotaliser32-bit unsigned, low word first
The datasheet saysThe device map says
40001, 40003 (a “4xxxx” number)address: 0, address: 2, and table: holding (the default). A number starting 4 is a holding register, 3 an input register, 1 a discrete input, 0 a coil. The register number minus 40001 is the address: 40001 is address 0.
32-bit floatformat: float32
32-bit unsignedformat: uint32
“low word first”, “little-endian words”, “CDAB”word-order: little on the device type
“scaled x10”, “in tenths”scale: 0.1
“write”, “setpoint”writable: true (a holding register or a coil only)

So the map is:

devices:
flow-meter:
word-order: little
registers:
- {tag: Flow, address: 0, format: float32, unit: "m3/h", desc: flow rate}
- {tag: Total, address: 2, format: uint32, desc: totaliser}
instances:
- {id: FM1, type: flow-meter, host: 127.0.0.1, port: 15021, unit-id: 1}
Terminal window
naut modbus import --map devices.yaml

The generated tags are FM1_Flow and FM1_Total: the instance id, an underscore, the register’s tag. Two meters of this type would be FM1_… and FM2_….

Never trust the word “low word first” alone; a datasheet can be wrong or read the other way. Start the bench device with a value you know, 1234.5:

Terminal window
echo '{"FM1_Flow": 1234.5, "FM1_Total": 70000}' > seed.json
naut modbus serve --manifest modbus_manifest.yaml --values seed.json --listen 127.0.0.1:15021

In another terminal, read the two registers of the float as a float32, first the default way (high word first), then low word first:

Terminal window
naut modbus browse --host 127.0.0.1 --port 15021 --unit 1 --from 0 --count 2 --format float32
naut modbus browse --host 127.0.0.1 --port 15021 --unit 1 --from 0 --count 2 --format float32 --word-order little
addr raw float32
0 0x5000 449A 8.60791808e+09
addr raw float32
0 0x5000 449A 1234.5

The same two registers, 0x5000 then 0x449A, are nonsense one way and exactly 1234.5 the other. The float 1234.5 is 0x449A5000; the device sends the low half, 0x5000, in register 0, which is what “low word first” means. With a real device you do not know the answer in advance, but the rule is the same: whichever reading gives a believable value is the word order. If a value is garbage whose size still looks plausible, try word-order: little first; if it is still wrong, the bytes inside each register are swapped too (byte-order: little).

Run naut modbus browse without --format to see every format at once, which finds a register’s real format in one look.

Run the controller against it, or read the Modbus guide for writes and per-tag quality.

nautilus is free and open source (Apache 2.0), built by Joy Automation. For implementation or support on your site, see Joy Automation services. Privacy.