PROFINET IO device (experimental)
With type: profinet-device, nautilus appears on a PROFINET network as
an IO device. A PLC (an S7-1500 in TIA Portal, for example) configures it
from a GSDML file like any other station, connects, and exchanges cyclic
data with it. Data flows both ways:
- The PLC’s outputs arrive as nautilus input tags.
- nautilus output tags are the PLC’s inputs.
The manifest
Section titled “The manifest”interface: eth1 # the NIC on the PROFINET networkstation: nautilus-1 # NameOfStation the PLC looks forvendor-id: 0x.... # what the GSDML and DCP say this device isdevice-id: 0x....min-cycle: 8ms # the shortest cycle offered (MinDeviceInterval)slots: - slot: 1 module-ident: 0x00000101 subslots: - {subslot: 1, submodule-ident: 0x00000001, inputs: 8, outputs: 4}tags: - {name: Bin1_Level, slot: 1, subslot: 1, dir: input, offset: 0, format: float32} - {name: Bin1_Fill, slot: 1, subslot: 1, dir: output, offset: 0, bit: 0, format: bool}Directions are the PLC’s, because that is how the GSDML and the engineering tool show them:
inputs:anddir: inputare data nautilus provides;outputs:anddir: outputare data the PLC commands.
Formats are bool (with bit: 0–7), int8, uint8, int16,
uint16, int32, uint32, int64, uint64, float32 and float64,
all big-endian as PROFINET is. naut check rejects a tag that overlaps
another or does not fit its subslot. The limits are 24 subslots and 244
bytes each way.
driver: type: profinet-device manifest: profinet_device.yamltag-files: [tags/profinet.yaml]naut profinet tags profinet_device.yaml # tags/profinet.yaml, IEC types, the PLC's outputs as inputsnaut profinet gsdml profinet_device.yaml # GSDML-V2.35-…xml for the engineering toolImport the GSDML into the engineering tool (TIA Portal: Options → Manage general station description files) and add the station. The GSDML and the driver come from the same manifest, so the PLC is configured with exactly the layout the driver serves. If they differ anyway, because the manifest changed and the GSDML was not re-imported, the device answers the connection with a module difference. The status row then says which modules differ, and their data is marked invalid both ways.
Update time. The GSDML offers RT_CLASS_1 at a 1 ms send clock with
reduction ratios 1, 2, 4 … 512, so the update times an engineering tool
can set are 1, 2, 4 … 512 ms, and never below min-cycle. When nautilus
configures a Siemens CPU itself (a profinet-manifest: device in the
CPU’s station, target: siemens), it also keeps to 16 ms or more, so the
allowed times are 16, 32, 64, 128, 256 and 512 ms. Any other time is
refused at deploy. With no update time set, the deploy picks the first
of those at or above min-cycle (min-cycle: 20ms gives 32 ms) and
writes it explicitly, so TIA never picks a faster one.
Privileges and the network
Section titled “Privileges and the network”PROFINET runs on raw Ethernet, so the process needs CAP_NET_RAW:
sudo setcap cap_net_raw+ep "$(command -v naut)"# or, under systemd: AmbientCapabilities=CAP_NET_RAWWithout it the project still loads, checks and runs. The driver’s status row says what is missing and the driver keeps retrying.
The connection setup (DCE/RPC) uses UDP 34964 on the host’s IP stack, so the interface needs an address on the PROFINET subnet. The port is opened only on the station’s own address, once the PLC has assigned it. It is never open on all of the host’s networks, and replies always come from the address the PLC talks to.
nautilus never changes the host’s network settings. A PLC assigns its devices’ IP addresses over DCP, and DCP has no authentication.
- An address assignment is accepted only when it names an address the interface already holds. Give the device that address in the PLC’s project.
- Any other assignment is refused, and the status row shows the refusal with the addresses the interface has.
- A station name the PLC assigns is used until restart and never saved. The manifest stays the source of truth.
Quality and the online tag
Section titled “Quality and the online tag”profinet_device__Online (or <driver name>__Online) is true while a PLC
holds an AR and its frames arrive.
The input tags (the PLC’s outputs) carry quality:
| Quality | When |
|---|---|
| NotConnected | Until the first good value. The tag reads its init:, as for every communications driver. |
| Good | The PLC is in run and its status for the subslot is good. |
| Bad | The PLC is in STOP, its status for the subslot is bad, or the module differs from the layout. |
| Stale | The connection ended: the PLC stopped sending, released it, or the cable is out. |
The last good value is held through Bad and Stale. When the connection
ends, the input tags go Stale with their last good value and
profinet_device__Online goes false. They read Good again only once a
new connection delivers fresh data.
The data nautilus provides is marked invalid to the PLC (IOPS bad) in three cases:
- until the program has written every output tag once;
- while the write gate is closed, for example when scans hang;
- after the gate reopens, until every output has been written again.
The PLC sees invalid data rather than zeros or a frozen value, and handles it as it would a faulty module.
Redundancy
Section titled “Redundancy”naut check still refuses PROFINET together with redundancy:. On
takeover the new leader must already hold the station’s address, and
redundancy: cannot name and check that floating address yet. What
follows is how it will behave once it can.
Under redundancy:, only the leader is a PROFINET device. Every frame
it sends first checks that its lease is still current, so a leader that
was frozen past its lease sends nothing when it resumes. A standby
holds no socket on the interface. It answers no DCP and sends no LLDP,
so two replicas never answer for one station name. Its input tags read
Stale and keep their last value, and its status row says standby.
On takeover:
- The old leader goes silent, and the PLC’s connection to it times out.
- The PLC looks for the station name again and finds it at the new leader’s MAC address.
- The PLC connects, and the data turns valid with the new leader’s first full push.
The PLC also assigns the station’s IP address again. nautilus accepts that only when the new leader’s interface already holds the address (see above), and two hosts cannot hold one address on one network at once. So for now, have the station’s address move with the leader (a floating address managed outside nautilus). Hand-over against a real PLC, including how long the PLC takes to reconnect, has not been measured yet.
What it does not do yet
Section titled “What it does not do yet”- Run with
redundancy:: refused until the floating station address can be named and checked (see above); the hand-over is not measured yet. - Be a PROFINET controller that drives devices. That comes next.
- IRT, MRP, system redundancy, PROFIsafe, more than one AR, alarms raised to the PLC, strings or arrays.
- Cycle times under 8 ms until measured on the target.
The design brief is docs/design/profinet.md.